C²DCS Meeting - February 2021

Europe/Berlin
ZOOM (online)

ZOOM

online

Description

a Cross Collaboration DCS meeting

  • CBM/mCBM
  • HADES
  • PANDA
  • R³B
  • ...

Monthly informal meeting series of DCS activists to exchange knowledgde, share experiences and work together on common issues.   

 

Zoom Coordinates: 

Topic: Florian Feldbauer's Zoom Meeting
        https://ruhr-uni-bochum.zoom.us/j/99929730827?pwd=eVpIZ2xrQmFwTUhpUm9sSmtwNTdLQT09 
        Meeting ID: 999 2973 0827
        Passcode: 874164
        One tap mobile 496938079883,,99929730827

Registration
Participants
    • 14:00 14:30
      HADES Test beamtime - DCS lessons learned / truisms "Binsenweisheiten" / anecdotes 30m

      HADES just finished its test beamtime (Feb 8-13, 2021) introducing and evaluating the performance of the new forward detectors together at maximum proton beam intensities 10⁸ and maximum beam energies of 4.2 GeV on an LH2 target.

      beam vs. equipment

      • again, while threading the beam to the target, powered LV devices (TDK lamdda) where hit by intense primary/secondary beam 2 out of 8 failed (positioned there for more then 15 years)
      • "again", since Mar2019, magnet failure in front of the cave, opened the way directly to a stack of ~10 TDK Lambda, ~4-5 broken, power amplifier.

      Options

      → evaluation of different positioning longer cables / rules for switching power
      → shielding
      → "TOP" principle (from OSH/"Arbeitsschutz"):Technical → Organizational (→ Personal))

      Silence

      • 1-wire sensors (performance & keep alive)
      • based on HadCon2: chained 1-wire bus readout of ADCs
      • EPICS uses streamDevice to communicate with HadCon2
      • record issues read command, every second.
      • HadCon2 (1-wire master) evaluates itself list of available devices and addresses and reads the values and publishes the results "en bloc".
      • StreamDevice triggers I/O Events to scan those results and processes only the relevant records.

      → Problem: no error recognition

      • If a sensor or the complete bus does not answer anymore, it is not recognized immediately, since it is not updated.

      → possible solutions:

      • single device read/response mechanism vs. performance?
      • regular separate device check, changing the error state of the value records.

      remotely switchable plugs

      • Latter problem was temporarily solved by power cycle to revive the HadCon2 connection

      → switchable plug plug + automatic IOC restart

      (this time no network issues)

      Speaker: Dr Peter Zumbruch (GSI Helmholtzzentrum für Schwerionenforschung GmbH(GSI))
    • 14:30 15:00
      a.o.b 30m